The following safety precautions should be taken when disintegrating GIS:
1, disassembling maintenance, maintenance personnel should wear special work clothes (protective clothing), hats, scarves. Gas mask or dust mask, using thin latex gloves or nylon gloves (not cotton yarn), goggles and special work shoes;
2, in and out of SF6 maintenance room, use the fan or compressed air to wash the whole body;
3. Wash hands frequently and the exposed part of the human body during work breaks, and pay attention to personal hygiene;
4, the workplace should be kept dry, clean and well ventilated;
5. Smoking and eating food are strictly prohibited in the workplace;
6, when the circuit breaker is disintegrated, it is found that there is white powdered decomposition inside, which should be wiped with a vacuum cleaner or soft toilet paper, and must not be removed by compressed air or other methods to make it fly;
7, the following items should be specially treated: suction in the vacuum cleaner, the filter of the gas mask, all the wipe cloth and paper, the adsorbent in the arc extinguishing room of the circuit breaker, the adsorbent in the filter of the gas recovery device, etc., can not be heated or incinerated on the spot, can be put into the steel container, centralized treatment
8, the adsorbent in the circuit breaker arc extinguishing room can not be dried and regenerated.